Rail and metro wiring
IS 17048:2018 LSZH for high-occupancy enclosed and underground transit where smoke and halogen limits drive specification. NBCS 2026 Part F Annex H-8.4 calls for LSZH armoured XLPE cable at enclosed metro stations.
Governing standards
Domestic supply
| Application | Cable | Specification |
|---|---|---|
| Underground stations — all occupied areas | LSZH / HFFR WireIS 17048:2018 | HFI-TP 70 thermoplastic. HCl ≤0.5%, light transmittance ≥70%, IEC 60332-1-2 flame tested |
| Surface station buildings — administrative blocks | FR-LSH Single Core WireIS 694:2010 | OI >29%, TI >250 °C, IEC 60332-1-2:2004 |
| Signalling, relay & interlocking circuits | Control CableIS 694:2010 | Class 5 flexible; screened variant for EMI-sensitive signalling environments |
| BMS & platform equipment circuits | Multicore Flexible CableIS 694:2010 | PVC insulated & sheathed, 2–24 cores |
| Station PABX & internal telephone | CW1308 Telephone CableBT CW1308 | Solid bare annealed copper; max 97.8 Ω/km conductor resistance |
H07Z1-K (EN 50525-3-31) is the international designation for LSZH flexible single-core wire produced on our IS 17048:2018 certified line — same zero-halogen, 70 °C thermoplastic HFFR construction (HFI-TP 70), documented for international tender submission.
View export & international standards →Reference clients
Related sectors
Rail & metro cable specification — common questions.
Sector-specific questions raised by metro, Indian Railways, and transit MEP procurement teams.
Which cable does NBCS 2026 call for at enclosed metro stations?
NBCS 2026 (SP 7:2026) Part F Annex H-8.4 calls for fire-resistant/fire-survival LSZH armoured XLPE cable for fire and life safety equipment at enclosed metro stations. The same annex calls for flame retardant LSZH armoured XLPE cable for other essential services at enclosed stations. At open stations, it calls for flame retardant, low smoke halogen free (FRLSH) armoured XLPE cable for power supply. Annex H-9(c) calls for fire-resistant LSZH wires for emergency lighting at underground stations.
Specify IS 17048:2018 LSZH (HCl ≤ 0.5%, light transmittance ≥ 70%) where the project specification limits halogen acid gas to 0.5%. Fire-survival capability is a separate requirement from IS 17048:2018.
What flame-spread evidence do metro tenders expect for grouped cables in station trays?
Metro tenders typically call for IEC 60332-3-24:2018 Category C evidence — bunched cable flame-spread limit of 1.5 L/m fuel — submitted alongside the single-cable test data per IEC 60332-1-2:2004.
National Cables supplies IS 17048:2018 type-test documentation (smoke transmittance, halogen emission, IEC 60332-1-2 single-cable flame test) with the BIS licence reference (CM/L-8800227819); state bunched-test (IEC 60332-3-24) requirements at the enquiry stage. Category C is the level tenders typically call for in dense station and tunnel tray installations.
Which standard governs station PABX and admin telephone distribution?
BT CW1308 governs station PABX, internal voice, and admin telephone distribution. CW1308 specifies:
- Solid bare annealed copper conductor (IEC 60228 Class 1)
- Maximum loop resistance 97.8 Ω/km
- Working voltage 80 V (signalling level, not power)
- Operating temperature range 0–70°C
For high-performance signal and data backbone, specify CW1293 (BT CW 1293 Issue 4) with tinned solid copper and TI54 insulation — used in data centres and exchange-MDF distribution.
Do surface station buildings use the same LSZH cable as underground stations?
Not necessarily. NBCS 2026 Part F Annex H-8.4 calls for flame retardant, low smoke halogen free (FRLSH) armoured XLPE cable for power supply at open stations, and LSZH armoured XLPE cable at enclosed stations. NBC 2016 does not set cable type by occupancy group. NBCS 2026 FRLSH is halogen free and differs from IS 694:2010 FR-LSH, which permits up to 20% halogen acid gas. Specify FR-LSH (IS 694:2010) for surface administrative, ticketing, and parking buildings only where the project specification permits it.
Specify LSZH (IS 17048:2018) for underground stations and enclosed tunnels where the project specification limits halogen acid gas to 0.5%. FR-LSH has a lower per-metre cost than LSZH.
Is National Cables' LSZH cable usable on international metro and rail projects?
Yes. H07Z1-K (EN 50525-3-31) is the international harmonised designation for LSZH single-core flexible wire — same zero-halogen, 70°C thermoplastic HFFR construction (HFI-TP 70) produced on the IS 17048:2018 certified line.
This enables seamless specification on cross-border metro and rail projects in GCC, African, and emerging-market transit systems. Type-test reports are issued in international tender format with the BIS licence reference.
Specify National Cables for your rail or metro project.
IS 17048:2018 type-test reports, IEC 60332-3 Category C evidence, and project pricing — 24-hour response.