Airport & Aviation · Terminals · IS 17048:2018

Airport terminal wiring

Specify IS 17048:2018 LSZH in occupied terminal areas where the project specification limits halogen acid gas to 0.5%. IS 17048:2018 also requires light transmittance of at least 70% through the smoke.

IS 17048:2018
HCl ≤0.5%, light transmittance ≥70%
IEC 60332-1-2
Single-cable flame test
IEC 60332-3
Cable tray bunched test
Sector Requirements

Governing standards

NBC 2016 · IS 17048:2018 · IEC 60332-3-24
NBC 2016 Part 8/Sec 2 cl. 5.3.7.1 states that it is desirable to use flame retardant cables and wires in electrical distribution systems.
Specify IS 17048:2018 HFFR in occupied terminal zones where the project specification limits halogen acid gas to 0.5%. Cables for fire alarm and PA systems shall be laid in metal conduit or armoured (NBC 2016 Part 4 cl. 3.4.6.2). BMS, fire-alarm, and HVAC control circuits use screened cable where the discipline drawings specify EMI shielding. Tray installations submit IEC 60332-3-24:2018 Category C evidence alongside single-cable tests.
IS 17048:2018NBC 2016 Part 8/Sec 2IEC 60332-3-24:2018IEC 61034-2Project specification

Products

Domestic supply

Application Cable Specification
All occupied terminal areas LSZH / HFFR WireIS 17048:2018 HFI-TP 70 thermoplastic. HCl <0.5%, smoke ≥70%, OI ≥31%, IEC 60332-1-2 flame tested
Airside & service area wiring FR-LSH Single Core WireIS 694:2010 OI >29%, TI >250 °C, IEC 60332-1-2:2004
BMS, fire alarm & HVAC control Control CableIS 694:2010 Class 5 flexible; screened variant for EMI-sensitive BMS and fire alarm systems
Equipment rooms & panel wiring Single Core Flexible WireIS 694:2010 Class 5, FR or FR-LSH
Terminal PABX & internal telephone CW1308 Telephone CableBT CW1308 Electro-tinned solid copper; <97.8 Ω/km loop resistance
Power distribution circuits Multicore Flexible CableIS 694:2010 PVC insulated & sheathed, 2–4 core

Export & International
International airport and terminal projects

H07Z1-K (EN 50525-3-31) and H07V-K (IEC 60227-3) to EN/IEC designations, produced from the same 1100 V-class certified line — documented for international tender submission.

View export & international standards →
Clients in This Sector

Reference clients

Delhi Airport
Terminal building wiring
Indian Railways
Station infrastructure

Frequently Asked Questions

Airport & aviation cable — common questions.

Specification questions raised by airport procurement teams and aviation MEP consultants.

Which cable type is specified for airport terminal occupied areas?

NBC 2016 does not assign a cable type to airport terminals, and IS 17048:2018 is not cited in NBC 2016. NBC 2016 Part 8/Sec 2 cl. 5.3.7.1 states that it is desirable to use flame retardant cables and wires, and that FR-LSH cable may be considered. Specify IS 17048:2018 LSZH in terminal areas where the project specification limits halogen acid gas to 0.5%.

IS 17048:2018 limits LSZH to halogen acid gas ≤ 0.5% and requires light transmittance ≥ 70% and Oxygen Index ≥ 31.

What flame-spread evidence do airport tenders typically require for tray installations?

Bunched cable installations on airport trays typically require IEC 60332-3-24:2018 Category C evidence — flame-spread limit 1.5 L/m fuel — submitted alongside single-cable test data per IEC 60332-1-2:2004. Category C is the appropriate level for grouped low-voltage cables in dense terminal trays.

National Cables supplies IS 17048:2018 type-test documentation (smoke transmittance, halogen emission, IEC 60332-1-2 single-cable flame test) with the BIS licence reference (CM/L-8800227819); state bunched-test (IEC 60332-3-24) requirements at the enquiry stage.

Which cable applies to BMS, fire alarm, and HVAC control circuits in airport buildings?

BMS, fire alarm, and HVAC control circuits use screened multicore control cable based on IS 694:2010 Class 5 flexible — typically with aluminium foil + tinned drain-wire for EMI shielding where the discipline drawings call for it.

Class 5 fine-strand construction handles repeated bending during panel installation; the screen prevents EMI coupling with sensitive 4–20 mA loops, RTD inputs, and Modbus / BACnet signal lines that share trays with VFD and high-current power feeders. Specify foil + drain with single-point screen earthing per the EMC plan.

Why is 1100 V-class IS 694:2010 specified rather than 600/1000 V cable?

Airport equipment rooms and panel wiring use IS 694:2010 1100 V-class insulation rather than 600/1000 V cable to provide margin against motor-start surges and switching transients common in aviation infrastructure (jet bridges, baggage conveyors, HVAC AHU motors).

The same 1100 V production line manufactures the export H07Z1-K (EN 50525-3-31) LSZH and H07V-K (IEC 60227-3) single-core wire — enabling consistent specification on cross-border terminal projects.

Is National Cables' wire eligible for international airport tenders?

Yes. H07Z1-K (EN 50525-3-31) LSZH single-core and H07V-K (IEC 60227-3) PVC single-core are produced from the same BIS-certified IS 17048:2018 and IS 694:2010 production lines and carry full international type-test documentation.

For airport projects in GCC, African, and European markets, these harmonised designations meet local specification practice without requiring cable redesign. Test certificates and material declarations are issued in tender-ready format.

Specify National Cables for your airport project.

IS 17048:2018 type-test reports, BIS compliance records, and project pricing — 24-hour response.