NBC 2016 Part 4 cl. 3.4.6.1 states that it is desirable for building wiring and cabling to have flame retardant property. NBC 2016 Part 8/Sec 2 cl. 5.3.7.1 notes that FR-LSH cable is available and may be considered.

NBC 2016
FR wiring desirable, Part 4 cl. 3.4.6.1
IS 17048:2018
Halogen-free wiring, HCl ≤0.5%
54 years
Delhi institutional supply
Sector Requirements

Governing standards

NBC 2016 Part 4 · IS 694:2010 · IS 17048:2018
NBC 2016 Part 4 cl. 3.4.6.1 states that it is desirable for wiring and cabling to have flame retardant property.
Medium and low voltage wiring in shafts and within false ceilings shall run in metal conduit (NBC 2016 Part 4 cl. 3.4.6.1). Power to fire and life safety panels shall be through fire-proof enclosures, circuit integrity cables to IS 16246, or an alternate route in the adjoining fire compartment (NBC 2016 Part 4 cl. 3.4.6.2). Specify FR-LSH to IS 694:2010 where the project specification limits halogen acid gas to 20%. Specify HFFR to IS 17048:2018 where the project specification limits halogen acid gas to 0.5%.
NBC 2016 Part 4IS 694:2010IS 17048:2018IS 10810 (Part 53)IS 10810 (Part 63)

Products

Domestic supply

Application Cable Specification
Fixed conduit wiring — general areas FR Single Core WireIS 694:2010 Class 2 conductor, ISI marked, BIS IS 694:2010 licence
Occupied floors, corridors, escape routes FR-LSH Single Core WireIS 694:2010 OI >29%, TI >250 °C, IEC 60754-1 halogen limit
High-rise, hospitals, places of assembly LSZH / HFFR WireIS 17048:2018 HFI-TP 70 halogen-free compound; HCl <0.5%, smoke ≥70%, OI ≥31%
HVAC, BMS & lighting control circuits Multicore Flexible CableIS 694:2010 PVC insulated & sheathed, 2–24 cores
Intercom, access control, nurse call Switchboard & Intercom CableTEC/ITD G/WIR-06/02 Electro-tinned solid copper; FR PVC sheath
Internal telephone, PABX distribution CW1308 Telephone CableBT CW1308 0.5 mm solid copper; <97.8 Ω/km; <56 nF/km
Engineering Note
MEP benchmark metrics
FR-LSH wire: OI ≥29% (IS 10810 Part 58:1998), TI ≥250 °C (IS 10810 Part 64:2003), halogen acid gas ≤20% (IS 10810 Part 59), smoke density rating ≤60% (IS 13360 Part 6/Sec 9), flammability per IS 10810 Part 53. LSZH: halogen acid gas ≤0.5% (IS 10810 Part 59), light transmittance ≥70% (IS 10810 Part 63). Each compound carries separate BIS licence and type-test evidence.
IS 694:2010IS 17048:2018IS 10810 Part 58:1998IS 10810 Part 64:2003IEC 60754-1NBC 2016 Part 8/Sec 2

Export & International
International building and MEP projects

The BIS IS 694:2010 production line also builds H07V-K (IEC 60227-3), NYY-J / NYY-O (IEC 60502-1), BS 6004 (BS 6004:2012), and NYM-J (DIN VDE 0250) for cross-border MEP projects.

View export & international standards →
Clients in This Sector

Reference clients

DLF Limited
Commercial real estate
Ansal Housing Group
Residential development
ITC Maurya
Five-star hotel, Delhi
Hotel Imperial
Five-star hotel, Delhi
Le Méridien
Five-star hotel, Delhi
Hotel Novotel
Hospitality
The Bharat Hotels
Hotel group
Kamal Developers
Construction

Frequently Asked Questions

Building & construction cable — common questions.

What MEP consultants, EPC contractors, and project procurement teams typically ask when specifying building wire.

Does NBC 2016 require FR-LSH instead of basic FR cable?

NBC 2016 Part 4 cl. 3.4.6.1 states that it is desirable for wiring and cabling to have flame retardant property. NBC 2016 Part 8/Sec 2 cl. 5.3.7.1 states that the availability of FR-LSH cable may be noted and considered. NBC 2016 does not set cable type by occupancy group or storey count. NBC 2016 Part 8/Sec 2 Annex B reproduces CEA Regulation 44(2)(x)(f), which calls for FRLS cable of two-hour rating for a substation in a basement.

Specify FR-LSH (IS 694:2010) where the project specification limits halogen acid gas to 20% and smoke density rating to 60%. National Cables suggests FR-LSH for occupied floors, corridors, escape routes, and lift lobbies.

What are the OI and TI thresholds for FR-LSH cable per IS 694:2010?

FR-LSH cable to IS 694:2010 must meet:

  • Oxygen Index ≥ 29% tested per IS 10810 (Part 58):1998
  • Temperature Index ≥ 250°C tested per IS 10810 (Part 64):2003
  • Halogen acid gas ≤ 20% per IS 10810 (Part 59)
  • Smoke density rating ≤ 60% per IS 13360 (Part 6/Sec 9)

These metrics verify the material's flame-retardant and thermal stability properties. Each compound carries separate BIS licence and type-test evidence.

When should I specify HFFR (IS 17048:2018) instead of FR-LSH?

Specify HFFR (IS 17048:2018) for hospitals, data centres, server rooms, underground metro stations, and any tender that calls for maximum smoke and halogen limits. HFFR is limited to 0.5% halogen acid gas and must reach light transmittance ≥ 70%. FR-LSH is limited to 20% halogen acid gas and a smoke density rating ≤ 60%, a different smoke test.

The HCl difference is critical where halogen acid gas would damage medical equipment, server hardware, or evacuation visibility in a fire. FR-LSH and HFFR carry separate BIS licences and are not interchangeable where a BOQ names one standard.

Can FR-LSH and LSZH cables be mixed in the same building project?

Yes — by zone. Typical specification practice in mixed-use buildings:

  • FR-LSH in occupied floors, corridors, escape routes, and lift lobbies
  • LSZH (IS 17048:2018) in server rooms, hospital wings, metro-linked plant rooms, and Tier-style data hall builds
  • Plain FR in back-of-house plant areas not accessible to occupants

The project's MEP fire schedule sets the cable type for each zone.

What documentation does National Cables provide for MEP / EPC tender submission?

For each cable category supplied, National Cables issues:

  • BIS licence reference: CM/L-8800140116 for IS 694:2010 cables; CM/L-8800227819 for IS 17048:2018 cables (verifiable at bis.gov.in)
  • Type-test reports per the relevant IS / IEC standards
  • Lot test certificates with conductor resistance, insulation resistance, and dimensional verification

All documentation is issued at order stage; no separate fee or qualification process is required.