What NBC 2016 says
about cables.
NBC 2016 Part 4 cl. 3.4.6.1 states that it is desirable for wiring and cabling to have flame retardant property. Part 8/Sec 2 cl. 5.3.7.1 states that it is desirable to use flame retardant cables and wires in electrical distribution systems. NBC 2016 does not assign FR, FR-LSH or HFFR cable by occupancy group or storey count. Its mandatory cable clauses cover power routing to fire and life safety systems, wiring in shafts, basement substations and lift supply cables. This page lists each clause.
What NBC 2016 says about FR and FR-LSH cable.
NBC 2016 Part 4 cl. 3.4.6.1 states: "In general, it is desirable that the wiring and cabling are with flame retardant property."
NBC 2016 Part 8/Sec 2 cl. 5.3.7.1 states that it is desirable to use flame retardant cables and wires in electrical distribution systems. The same clause states that the availability of flame retardant low smoke and halogen cable may also be noted and considered.
Part 8/Sec 2 cl. 2.1.15 and cl. 2.1.16 define FR cable and FR-LSH cable by reference to IS 694:2010.
Part 4 cl. 3.1.1 classifies buildings into nine occupancy groups: A Residential, B Educational, C Institutional, D Assembly, E Business, F Mercantile, G Industrial, H Storage and J Hazardous. NBC 2016 does not assign a cable type to any of these groups.
Part 4 cl. 2.38 defines a high-rise building as 15 m or above in height. NBCS 2026 (SP 7:2026) Part F cl. 2.39 sets this threshold at 24 m.
Part 4 cl. 3.4.6.1 and Part 8/Sec 2 cl. 5.3.7.1 use the word "desirable" for flame retardant cable. The requirements in the table below use the word "shall".
Cable requirements in NBC 2016 and NBCS 2026, by clause.
This table lists each cable requirement with its clause. NBCS 2026 rows are marked separately.
| Location or System | Requirement | Clause | Notes |
|---|---|---|---|
| Wiring and cabling, general | FR desirable | NBC 2016 Part 4, cl. 3.4.6.1; Part 8/Sec 2, cl. 5.3.7.1 | Advisory. FR-LSH availability "may also be noted and considered accordingly" (cl. 5.3.7.1). |
| Medium and low voltage wiring in shafts and false ceilings | Metal conduit | NBC 2016 Part 4, cl. 3.4.6.1 | — |
| Medium and low voltage wiring in shafts or ducts | Armoured, or run through metal conduit | NBC 2016 Part 4, cl. 3.4.5.4 | — |
| Power supply to fire and life safety panels and distribution boards | Fire-proof enclosures, circuit integrity cables, or alternate route in the adjoining fire compartment | NBC 2016 Part 4, cl. 3.4.6.2; Part 8/Sec 2, cl. 4.2.1(29) | Circuit integrity cable: IS 16246:2015. |
| Fire alarm and PA system cables | Metal conduit, or armoured | NBC 2016 Part 4, cl. 3.4.6.2; Part 8/Sec 2, cl. 4.2.1(29) | Physical segregation from power cables. |
| Substation in a basement | FRLS, 2-hour rating | NBC 2016 Part 8/Sec 2, Annex B | Extract of CEA Regulation 44(2)(x)(f). |
| Lift main power supply cables | Flame retardant PVC or XLPE insulated, armoured | NBC 2016 Part 8/Sec 5A, cl. 6.2.3 | — |
| Enclosed metro stations: fire and life safety equipment | Fire-resistant/fire-survival LSZH, armoured, XLPE insulated | NBCS 2026 Part F, Annex H-8.4 | NBCS 2026 (SP 7:2026). |
| Enclosed metro stations: other essential services | FR LSZH armoured, XLPE insulated | NBCS 2026 Part F, Annex H-8.4 | NBCS 2026 (SP 7:2026). |
| Open metro stations: power supply | FRLSH armoured, XLPE insulated | NBCS 2026 Part F, Annex H-8.4 | NBCS 2026 (SP 7:2026). |
| Underground metro stations: emergency lighting wiring | Fire-resistant LSZH wires | NBCS 2026 Part F, Annex H-9(c) | NBCS 2026 (SP 7:2026). |
Choosing FR, FR-LSH or HFFR: National Cables guidance, not a code requirement.
NBC 2016 cable clauses — common questions.
What NBC 2016 and NBCS 2026 say about cable type, with the clause for each answer.
Does NBC 2016 require FR-LSH cable in high-rise buildings?
NBC 2016 Part 8/Sec 2 cl. 5.3.7.1 states that it is desirable to use flame retardant cables and wires in electrical distribution systems.
The same clause states that the availability of flame retardant low smoke and halogen (FR-LSH) cable may also be noted and considered.
NBC 2016 Part 4 cl. 2.38 defines a high-rise building as 15 m or above in height, irrespective of occupancy.
NBCS 2026 (SP 7:2026) Part F cl. 2.39 sets the high-rise threshold at 24 m.
Neither code assigns a cable type by building height or storey count.
Does NBC 2016 require HFFR cable to IS 17048:2018 in hospitals or data centres?
IS 17048 is not cited in NBC 2016, its Amendment No. 1 (2021), or NBCS 2026 Part F.
NBC 2016 Part 4 cl. 3.1.1 places hospitals and sanatoria in Group C, subdivision C-1.
NBC 2016 does not assign a cable type to any occupancy group.
National Cables selection guidance: specify HFFR to IS 17048:2018 where the project specification limits halogen acid gas to 0.5%.
FR-LSH to IS 694:2010 has a halogen acid gas limit of 20% by weight (IS 694:2010 cl. 10.6).
Which NBC 2016 cable requirements are mandatory?
Part 4 cl. 3.4.6.2: power to fire and life safety panels shall be through fire-proof enclosures, circuit integrity cables (IS 16246), or an alternate route in the adjoining fire compartment.
Part 4 cl. 3.4.6.2: fire alarm and PA cables shall be laid in metal conduit or be armoured.
Part 4 cl. 3.4.5.4: medium and low voltage wiring in shafts or ducts shall be armoured or run through metal conduit.
Part 8/Sec 2 Annex B (extract of CEA Regulation 44(2)(x)(f)): a substation in a basement uses FRLS cable of two-hour rating.
Part 8/Sec 5A cl. 6.2.3: lift supply cables shall be flame retardant PVC or XLPE insulated armoured cables.
What cables does NBCS 2026 specify for metro stations?
NBCS 2026 (SP 7:2026) Part F Annex H-8.4 covers cables at metro stations.
Enclosed stations: fire-resistant/fire-survival LSZH armoured XLPE cables for fire and life safety equipment.
Enclosed stations: flame retardant LSZH armoured XLPE cables for other essential services.
Open stations: FRLSH armoured XLPE cables for power supply.
Annex H-9(c): fire-resistant LSZH wires for emergency lighting at underground stations.
National Cables holds BIS licences for both IS 694:2010 and IS 17048:2018.
FR and FR-LSH to IS 694:2010 (licence CM/L 8800140116). HFFR to IS 17048:2018 (licence CM/L 8800227819).